Note how the number 10 bare copper ground wire is shaped in the rear of the generator inlet box and then wrapped around the green ground screw using the included clamp.

This is an older house. The orange 10/3 Romex stands out against some of the original wiring and pipes.

See the 10/3 Romex cable fit in between the existing cables leaving the Cutler Hammer loadcenter.
The generator circuit breaker with the wires attached. The space below the generator breaker is needed for the operation of the interlock kit. Note the label above the Ideal 30-454 Wing-Nut Blue Wire Connectors. It is attached to a strap that is holding the generator circuit breaker in place and is required as per the interlock kit instructions. Without the label attached, this interlock kit installation would fail the electrical inspection